251401 Apollo Output Unit

Honeywell Eltek 251401 — Eltek Apollo output units communicate on fire loop to ANX95 and Delta DA apollo. The device is an output/relay output device that is supported by FireWin Explorer. Discontinued by Honeywell — no longer in the current range. PartnerPLC sources new, surplus and discontinued Honeywell parts — request a quote for price, condition and lead time.

Apollo Output Unit communicates on fire loop to ANX95 and Delta DA apollo. The device is an output/relay device that is supported by FireWin Explorer, is polarity dependent and is connected to the fire loop on terminals L+ and L-. The address is programmed via the DIP switch on the device itself. Monitoring resistor 6K2 is connected directly to terminals IP+ and IP- for unit monitoring. For functions other than output/relay output, use the Apollo Switch monitor or Zone monitor. Honeywell Eltek 251401 — Eltek Apollo output units communicate on fire loop to ANX95 and Delta DA apollo. The device is an output/relay output device that is supported by FireWin Explorer. Discontinued by Honeywell — no longer in the current range. PartnerPLC sources new, surplus and discontinued Honeywell parts — request a quote for price, condition and lead time.